Cleanline
Model TR-6000
Power Rating
6kVA/6000W
Input
Vlotage 110-300Vac at 50% load, 160-300Vac at 100% load
Frequency 50 or 60Hz ±10%
Phase Single phase with ground
Power factor >0.99 @ nominal voltage (100% Load)
Thdi ≤4% @ nominal voltage (100% Load)
Output
Voltage 208/220/230/240Vac
Voltage regulation ±1%
Frequency 50 or 60Hz ±0.1% (Battery mode)
Overload recovery Auto transfer to UPS
UPS Design Technology True on-line double conversion, Full digitized microprocessor controlled
Crest factor 3 : 1
Hamonic distortion ≤2% THD (Linear load), ≤4% THD (Non-Linear load)
Output waveform Pure sinewave
Transfer time 0 ms
Efficiency
AC mode >94%, Battery mode >91%, ECO mode > 96%
Protection and Filtering
Surge protection 220V (IEEEC6100-4-5 level 3)
Overload protection UPS Automatic bypass if overload between 110% to 130% at 30 seconds and more than 130% at 1.5 seconds
Short circuit protection UPS Output cut off immediately or input fuse/circuit breaker protection
Battery
Type Sealed, Maintenance-free lead acid batteries
Typical recharge time to 90% 8 hrs
Management Self-test
Battery protection Cut off without draining any current when battery is low
Cold start (DC start) yes
Back up time 15-30 minutes (Depending on computer load)
Expansion back up time Depending on customer required
Indicators
Status UPS status, Load level, Battery level, Input/output voltage, Remaining backup time, and Fault conditions
Audible Alarm
Battery mode Sounding every 4 seconds
Low battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
Diminsion 600 x 438 x 88 (2U) mm, Weight 15 Kgs ( without battery )
Environmental
Operating Temperature 0-40 °c
Relative humidity 0-95% (Non-Condensing)
Noise level <45dB@1 Meter
Interface
Smart RS232 Software supports windows family, Linux, Sun solarris,
IBM aix, Compaq true64, SGI IRIX, FreeBSD, HP-UX and MAC
USB Windows family and MAC OS
SNMP(option )Power management from SNMP manager and web browser
2 years warranty ( Onsite service )