Liebert ITA2-20KVA - Tower / Rack
Liebert ITA2-20KVA - Tower / Rack  ( rear)
Click เพื่อดูรุ่นอื่น
ลูกค้าสามารถติดต่อ เพิ่มเติมได้ที่  088 758 4005    080 964 2745    096 308 9747    088 758 4003    088 758 4005    080 964 2745   
World

ThailandUPS.com

ffice hours : 8:30 - 17:30 ( Monday - Friday )
Tel 0 2952 7823
เครื่องสำรองไฟ liebert

[ITA2-20kVA]



ITA20k00AL3A02P00


Part number 01202683
Liebert
Output Power Capacity  20kWatt / 20kVA
Topology  doubleconversion
Control Panel  LCD

Input Parameters

Nominal Input Voltage (V) 380/400/415 VAC 3-Phase, 4 Wire
Input Voltage Range (V)176-288 VAC at full load; 100-176 VAC at linear derating; 100 VAC at half load
Nominal Input Frequency (Hz)50/60
Input Frequency Range (Hz)40-70
Input Power Factor (kW/kVA)  0.99
Current THD at full linear load < 3
Battery

Battery Blocks Per String  24*, 30, 32, 34, 36, 38, 40
Battery Charger Max. Power (A) 8  
Battery Option P/C :
            ITA-BCI0020K01 ( built-in battery module of 16 block X  12 V X 9 AH)
            Battery cabinet Dimensions in rack arrangement - 430 (W) x 750 (D) x 85 (H)  
Output

Nominal Output Voltage (V)  220/230/240 VAC (1-Phase), 380/400/415 VAC (3-Phase)
Nominal Output Frequency (Hz)50/60
Rated Power Factor (kW/kVA)  Unity
Voltage Harmonic Distortion (%)<2% for Linear loads & <5% for Non-linear loads
Overload Capacity @ at 25 °C 105~125%, 10 min; 125~150%, 1 min
; >150%, 200 ms
Efficiency

Online Mode EfficiencyUp to 96.2%
ECO Mode EfficiencyUp to 99%
Dimensions and Weight Dimensions (W x D x H) in mm-Rack
Mounted Arrangement  430 x 600 x 130
Weight (kg)23
General

Nosie at 1 m (dBA)<58
Operating Temperature (°C)0 ~ 50*
Relative Humidity (%RH)5 ~ 95, non-condensing
Altitude (m)3000 without derating
General and safety requirements for UPS IEC/EN 62040-1
EMC requirements for UPS IEC/EN 62040-2
UPS classification according to  IEC 62040-3VFI-SS-111
3 years warranty + free startup


Available in different wattage variations, Vertiv™ Liebert® ITA2 is ideal in the edge of networks, light industrial applications and data centers, easily blending into any virtualized environment and providing comprehensive power protection at reduced operating costs.
Reliability in a compact footprint
Fully-digital control with high output voltage precision 
Manages all the nine power problems including sagging, spikes, and fluctuations
Built-in intelligent communication card for remote monitoring and management
Built-in-power charger for fast charging reduces the battery charging time
Prolonged backup time through cascaded connection
Quality-tested for 1000 hours for extreme durability and tolerance even in stringent conditions

High Availability


Early Warning of UPS System
Status Multiple audible and visual alarms instantly alert for critical issues.
Periodic Battery Testing

Provides automatic and manual self-diagnostic battery testing for peace of mind.
Power-Factor Correction

Prevents noise, harmonics, and distortion from being transferred to connected loads or fed back to the utility.
Lightning and Surge Protection

The transient voltage surge suppression circuitry inside the Liebert® ITA2 provides additional protection for the connected equipment.
Wide Input Voltage Window

Prolongs battery life by allowing the UPS to maximize the use of utility power before being transferred to the battery when the input voltage exceeds the specified limits.