[ITA2-5kVA]
ITA-05k00AL1102P00
Part number 01202670
Liebert
Output Power Capacity 5000Watt / 5000VA
Topology doubleconversion
Control Panel LCD
Input Parameters
Nominal Input Voltage (V)220/230/240 VAC 1-Phase, 2 Wire
Input Voltage Range (V)176-288 VAC at full load; 100-176 VAC at linear derating; 100 VAC at half load
Nominal Input Frequency (Hz)50/60
Input Frequency Range (Hz)40-70
Input Power Factor (kW/kVA) 0.99
Current THD at full linear load < 3
Battery
Battery Blocks Per String12*, 15, 16, 17, 18, 19, 20
Battery Charger Max. Power (A) 5
Battery Option P/C :
ITA-BCI0020K01 ( built-in battery module of 16 block X 12 V X 9 AH)
Battery cabinet Dimensions in rack arrangement - 430 (W) x 750 (D) x 85 (H)
Output
Nominal Output Voltage (V)220/230/240 VAC (1-phase)
Nominal Output Frequency (Hz)50/60
Rated Power Factor (kW/kVA) Unity
Voltage Harmonic Distortion (%)<2% for Linear loads & <5% for Non-linear loads
Overload Capacity @ at 25 °C 105~125%, 10 min; 125~150%, 1 min; >150%, 200 ms
Efficiency
Online Mode EfficiencyUp to 95.5%Up
ECO Mode EfficiencyUp to 99%
Dimensions and Weight Dimensions (W x D x H) in mm-Rack
Mounted Arrangement430 x 480 x 85
Weight (kg)11
General
Nosie at 1 m (dBA)<55
Operating Temperature (°C)0 ~ 50*
Relative Humidity (%RH)5 ~ 95, non-condensing
Altitude (m)3000 without derating
General and safety requirements for UPS IEC/EN 62040-1
EMC requirements for UPS IEC/EN 62040-2
UPS classification according to IEC 62040-3VFI-SS-111
3 years warranty + free startup
Available in different wattage variations, Vertiv™ Liebert® ITA2 is ideal in the edge of networks, light industrial applications and data centers, easily blending into any virtualized environment and providing comprehensive power protection at reduced operating costs.
Reliability in a compact footprint
Fully-digital control with high output voltage precision
Manages all the nine power problems including sagging, spikes, and fluctuations
Built-in intelligent communication card for remote monitoring and management
Built-in-power charger for fast charging reduces the battery charging time
Prolonged backup time through cascaded connection
Quality-tested for 1000 hours for extreme durability and tolerance even in stringent conditions
High Availability
Early Warning of UPS System
Status Multiple audible and visual alarms instantly alert for critical issues.
Periodic Battery Testing
Provides automatic and manual self-diagnostic battery testing for peace of mind.
Power-Factor Correction
Prevents noise, harmonics, and distortion from being transferred to connected loads or fed back to the utility.
Lightning and Surge Protection
The transient voltage surge suppression circuitry inside the Liebert® ITA2 provides additional protection for the connected equipment.
Wide Input Voltage Window
Prolongs battery life by allowing the UPS to maximize the use of utility power before being transferred to the battery when the input voltage exceeds the specified limits.